Skip to content

Conversion technologies

Conversion technologies step in the scenario editor

Conversion technologies are systems that transform one or more energy carriers into different types. For example, a gas boiler converts natural gas to heat. Each technology is defined by:

  • Technical parameters: efficiencies and technical limits.
  • Financial and environmental parameters: investment costs (CAPEX), operational costs (OPEX), and embodied emissions.

For parameters, see Conversion technology parameters.

Technology modes

A mode represents a specific operational regime with its own set of inputs, outputs, and efficiencies. A single technology can have multiple modes to reflect different operating regimes.

Example: a reversible heat pump has a heating mode and a cooling mode, each with a distinct coefficient of performance (COP). Only one investment is made and two behaviors are possible.

Tip

Technical parameters such as efficiency and capacity only affect the mode they are assigned to. Financial and environmental parameters affect all of the modes of the technology.

Primary vs. non-primary modes

  • Primary mode: has an impact on the installed capacity of the technology, which is reflected in the costs and CO2 emissions.
  • Non-primary mode: does not affect the installed capacity of the technology. The technology's investment or operational costs, or its CO2 emissions are not affected by the capacity of non-primary modes.

Tip

In most multi-mode use cases, each mode should be set as a primary mode.

Mode capacity

The capacity of a mode is the maximum of the hourly sum of all primary outputs of that mode.

You can choose different sizing methods:

  • Optimize capacity: Sympheny finds the optimal capacity.
  • Minimum and Maximum capacity: You can enter a minimum and/or maximum capacity bound.
  • Can be installed and Minimum capacity: If a minimum capacity is specified and the default option Default option toggle is toggled, the installed capacity can either be 0 or greater than the minimum.
  • Must be installed and Minimum capacity: The capacity must be greater than or equal to the minimum capacity.
  • Specify capacity: The installed capacity is fixed. If the default "can be installed" option is toggled, the capacity will be either 0 or the specified capacity.

Note

Operating capacity (which does not influence investment costs) may be equal to or lower than installed capacity.

Tip

For more advanced users, specifying a minimum and maximum capacity is good practice and often reduces computation time.

Technology capacity

The installed capacity of the technology is used to calculate the investment, maintenance costs, and embodied emissions. The technology capacity is the maximum of the hourly sum of all primary outputs of all primary modes. It is expressed in kW-output.

Example calculation

  • Mode A peak (primary): 100 kW at hour 5.
  • Mode B peak (primary): peak of 200 kW at hour 10.
  • Mode A + Mode B peak: at hour 8, modes A and B produce a combined 250 kW.

Result: the technology capacity is 250 kW.

Mode efficiency

The efficiency of a mode indicates energy dissipation within systems. The sum of output efficiencies represents the mode's total efficiency:

  • A total efficiency of 100% means useful energy is conserved.
  • A total efficiency below 100% indicates useful energy is lost in the system, for example heat losses in the technology, which are not modeled as a "waste heat" flow.
  • A total efficiency above 100% indicates useful energy is created within the system, for example useful heat extracted from the environment, which is not modeled as an "ambient air" flow.

Example: heat pump

The efficiency of a standard input (with two inputs) is set as follows:

Input EC Input share Output EC Output efficiency [%]
Electricity 100 HT heat 100
Ambient heat 200

The calculation is:

Output EC(i) = Sum of inputs × efficiency output(i)

HT heat = (100 + 200) × 100% = 300

In this case, 100 units of electricity and 200 units of ambient heat produce 300 units of HT heat. This corresponds to a COP of 3 (yearly average). See illustration below on how to set these parameters in the web-app.

Heat pump efficiency entered in the app

Example: chiller

For chillers, there are two ways to model cooling energy. The first method treats cooling energy as a service, meaning the energy is generated and supplied. For example, when modeling a chiller with an energy efficiency ratio (EER) of 2, the process is as follows:

Input EC Input share Output EC Output efficiency [%]
Electricity 100 HT heat 300%
Cooling 200%

This means that an input of 100 units of electricity produces 200 units of cooling (based on an EER of 2) and 300 units of heating (assuming the electricity is fully dissipated as heat).

100 units of electricity give, in this case, 300 units of HT heat and 200 units of cooling, from which an EER of 2 is calculated. Here, the cumulative output efficiency is greater than 100%, which reflects the "creation" of energy because cooling energy is treated as an additional service. See illustration below on how to set these parameters in the web-app.

Chiller efficiency entered in the app

Alternative method: chiller

There's also an alternative method where cooling energy is treated as an extraction of energy demand. To use this method, set the cooling demand to "reversed." In this case, the chiller can be modeled as a heat pump with an EER of 2 (or a COP of 3).

Input EC Input share Output EC Output efficiency [%]
Electricity 100 HT heat 100%
Cooling 200

See illustration below on how to set these parameters in the web-app.

Alternative chiller method entered in the app

Tip

For this method, it's crucial that the reverse box is ticked for the cooling demand in the Energy Demands step. This treats cooling as an extraction of heat.

Reverse checkbox in Energy Demands step

Simultaneity of operation

Different modes can operate simultaneously. To prevent this, leave the simultaneous checkbox unchecked, indicating the mode cannot run with others. This may increase optimization time.

Simultaneous operation checkbox

Alternatively, a less computationally intensive option is to define a different seasonal or hourly operation for each mode.

Some advanced parameters are not available to all plan tiers, but can be added through add-on options. Contact customer support for a demo and to discuss customizing these options to your needs.

Seasonal and hourly parameters

You can enter time-varying efficiencies, either as monthly or hourly values. To do so, select Time varying instead of Fixed for the output EC efficiency.

Time-varying efficiency setting

Example: air-source heat pump

For heat pumps, if you want to apply a time-varying COP, modify the input EC share rather than the output efficiency. The input EC share is what defines the COP (= heat HT / electricity). See the example below:

Time-varying input EC share for a heat pump

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Electricity 100 100 100 100 100 100 100 100 100 100 100 100
Heat ambient 100 150 150 200 200 250 250 250 200 150 100 100
HT heat 100% (stays fixed)
COP 2 2.5 2.5 3 3 3.5 3.5 3.5 3 2.5 2 2

Resulting COP curve for a heat pump